Fault analysis of the Gautrain 2 × 25 kV AC traction power supply system using disturbance fault records and on-site testing

dc.contributor.authorMoyo, Ndaedzo M.
dc.contributor.authorBansal, Ramesh C.
dc.contributor.authorNaidoo, Raj
dc.contributor.emailraj.naidoo@up.ac.zaen_ZA
dc.date.accessioned2021-06-11T13:45:56Z
dc.date.available2021-06-11T13:45:56Z
dc.date.issued2021-12
dc.description.abstractA typical 2 × 25 kV traction power supply system consists of both primary and secondary equipment housed in control rooms, and the traction overhead wiring (OHW) that runs between the substations. The substation secondary equipment consists of the protection and control intelligent electronic devices (IEDs) known as relays. Each section of the OHW between the substations is protected by a set of two relays at both ends of a line for impedance protection and their backup relays. At substations facing the sections at the end of the line, where there is no other substation on the other end, usually the overcurrent and earth fault protection is used. At the substations, there are disturbance fault recorders installed or relays equipped with a capability to record and store disturbance fault records. An analysis of these fault records makes a significant contribution to the efficient running of a traction system such as the Gautrain rapid rail system. A combination of the analysis of the faults that occur in the OHW as recorded and stored in the relays as well as the performance of the IEDs and the protection settings using the on-site tests are a subject of this article.en_ZA
dc.description.departmentElectrical, Electronic and Computer Engineeringen_ZA
dc.description.librarianhj2021en_ZA
dc.description.urihttp://ieeexplore.ieee.org/xpl/RecentIssue.jsp/?punumber=4267003en_ZA
dc.identifier.citationMoyo, N., Bansal, R. & Naidoo, R. 2021, 'Fault analysis of the Gautrain 2 × 25 kV AC traction power supply system using disturbance fault records and on-site testing', IEEE Systems Journal, vol. 15, no. 4, pp. 5704-5713.en_ZA
dc.identifier.issn1932-8184 (print)
dc.identifier.issn1937-9234 (online)
dc.identifier.other10.1109/JSYST.2020.3033885
dc.identifier.urihttp://hdl.handle.net/2263/80295
dc.language.isoenen_ZA
dc.publisherInstitute of Electrical and Electronics Engineersen_ZA
dc.rights© 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.en_ZA
dc.subjectAutotransformeren_ZA
dc.subjectTraction power suppliesen_ZA
dc.subjectSubstation protectionen_ZA
dc.subjectPower system protectionen_ZA
dc.subjectOverhead wiringen_ZA
dc.subjectOn-site testsen_ZA
dc.subjectGrounden_ZA
dc.subjectFeederen_ZA
dc.subjectFault analysisen_ZA
dc.subjectDisturbance fault record (DFR)en_ZA
dc.subjectCatenaryen_ZA
dc.subjectCurrent transformers (CTs)en_ZA
dc.subjectRelaysen_ZA
dc.subjectCircuit faultsen_ZA
dc.subjectSubstationsen_ZA
dc.subjectImpedanceen_ZA
dc.subjectRailsen_ZA
dc.subjectProtective relayingen_ZA
dc.titleFault analysis of the Gautrain 2 × 25 kV AC traction power supply system using disturbance fault records and on-site testingen_ZA
dc.typePostprint Articleen_ZA

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Moyo_Fault_2021.pdf
Size:
923.57 KB
Format:
Adobe Portable Document Format
Description:
Postprint Article

License bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
license.txt
Size:
1.75 KB
Format:
Item-specific license agreed upon to submission
Description: