Void fraction measurements of refrigerant flow in small diameter tubes using a capacitive sensor

dc.contributor.authorDe Kerpel, K.
dc.contributor.authorDe Paepe, M.
dc.date.accessioned2014-12-15T07:21:56Z
dc.date.available2014-12-15T07:21:56Z
dc.date.issued2012
dc.description.abstractPaper presented at the 9th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics, Malta, 16-18 July, 2012.en_ZA
dc.description.abstractThe void fraction is one of the key parameters in two phase flows. Quite a few methods have been proposed to measure this void fraction. Yet many of these methods are quite complex, intrusive and/or are not applicable to all possible void fraction ranges. Capacitance measurements have already been shown to characterize the two phase flow behaviour of refrigerants. Due to the curvature of the electrodes for circular tubes, the measured capacitance does not vary linearly with the void fraction. In this work a method is proposed to calibrate a capacitive sensor and thus determine the void fraction based on capacitive measurements. The proposed method was applied to 270 measurement points. The tube diameter D for all these points is 8mm, the mass flux ranges from 200 to 500 kg/m²s and the vapour fraction ranges between 2.5% and 97.5%. Refrigerants R134a and R410A were used. The results for these data points were compared to the Rouhani-Axelsson drift flux void fraction model. A very good agreement with this model was observed.en_ZA
dc.description.librariandc2014en_ZA
dc.format.extent9 pagesen_ZA
dc.format.mediumPDFen_ZA
dc.identifier.citationDe Kerpel, K & De Paepe, M 2012, Void fraction measurements of refrigerant flow in small diameter tubes using a capacitive sensor, Paper presented to the 9th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics, Malta, 16-18 July, 2012.en_ZA
dc.identifier.isbn9781868549863
dc.identifier.urihttp://hdl.handle.net/2263/42966
dc.language.isoenen_ZA
dc.publisherInternational Conference on Heat Transfer, Fluid Mechanics and Thermodynamicsen_ZA
dc.relation.ispartofHEFAT 2012en_US
dc.rightsUniversity of Pretoriaen_ZA
dc.subjectVoid fractionen_ZA
dc.subjectTwo phase flowsen_ZA
dc.subjectCapacitance measurementsen_ZA
dc.subjectRouhani-Axelsson drift flux void fraction modelen_ZA
dc.titleVoid fraction measurements of refrigerant flow in small diameter tubes using a capacitive sensoren_ZA
dc.typePresentationen_ZA

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
de_kerpel_void_2014.pdf
Size:
454.5 KB
Format:
Adobe Portable Document Format
Description:
Void fraction measurements of refrigerant flow in small diameter tubes using a capacitive sensor