Optimal network topology and reliability indices to be used in the design of power distribution networks in oil and gas plants

Show simple item record

dc.contributor.author Naidoo, Robin
dc.contributor.author Manning, E.J. (James)
dc.date.accessioned 2016-10-19T07:54:58Z
dc.date.available 2016-10-19T07:54:58Z
dc.date.issued 2013-02
dc.description.abstract The cost of loss of production in oil and gas plants is on average 6.5 times higher than that of plants in any other industry. Thus the reliability performance and analysis of oil and gas plants are unique. There have been many studies that have produced reliability indices for equipment that is used in industrial distribution networks, but these are all industry generic and none are specifi c to the oil and gas industry. This paper presents a set of equipment reliability indices that has been established from data collected from oil and gas plants and is suitable for use in reliability evaluations of the distribution networks of oil and gas plants. In the design of distribution networks for new oil and gas plants, engineers either do not have enough operational data, enough time or do not know how to perform the analysis required for establishing what type of network topology to use. This paper recommends the optimal network topology to use in such cases and provides evidence to support this proposal. en_ZA
dc.description.department Electrical, Electronic and Computer Engineering en_ZA
dc.description.librarian hb2016 en_ZA
dc.description.uri http://www.tandfonline.com/loi/tele20 en_ZA
dc.identifier.citation R Naidoo & E J Manning (2013) Optimal Network Topology and Reliability Indices to be used in the Design of Power Distribution Networks in Oil and Gas Plants, Australian Journal of Electrical and Electronics Engineering, 10:2, 239-249 DOI :10.7158/1448837X.2013.11464374. en_ZA
dc.identifier.issn 1448-837X (print)
dc.identifier.issn 2205-362X (online)
dc.identifier.other 10.7158/1448837X.2013.11464374
dc.identifier.uri http://hdl.handle.net/2263/57359
dc.language.iso en en_ZA
dc.publisher Taylor and Francis en_ZA
dc.rights © Institution of Engineers Australia, 2013. This is an electronic version of an article published in Australian Journal of Electrical and Electronics Engineering, vol. 10, no. 2, pp. 239-250, 2013. doi : 10.7158/1448837X.2013.11464374. Australian Journal of Electrical and Electronics Engineering is available online at : http://www.tandfonline.com/loi/tele20. en_ZA
dc.subject Failure rate en_ZA
dc.subject Mean time to repair en_ZA
dc.subject Inherent availability en_ZA
dc.subject Cost of loss of production en_ZA
dc.subject Capital cost en_ZA
dc.subject Total cost of ownership en_ZA
dc.title Optimal network topology and reliability indices to be used in the design of power distribution networks in oil and gas plants en_ZA
dc.type Postprint Article en_ZA