Fault analysis of the Gautrain 2 × 25 kV AC traction power supply system using disturbance fault records and on-site testing

Show simple item record

dc.contributor.author Moyo, Ndaedzo M.
dc.contributor.author Bansal, Ramesh C.
dc.contributor.author Naidoo, Raj
dc.date.accessioned 2021-06-11T13:45:56Z
dc.date.available 2021-06-11T13:45:56Z
dc.date.issued 2021-12
dc.description.abstract A typical 2 × 25 kV traction power supply system consists of both primary and secondary equipment housed in control rooms, and the traction overhead wiring (OHW) that runs between the substations. The substation secondary equipment consists of the protection and control intelligent electronic devices (IEDs) known as relays. Each section of the OHW between the substations is protected by a set of two relays at both ends of a line for impedance protection and their backup relays. At substations facing the sections at the end of the line, where there is no other substation on the other end, usually the overcurrent and earth fault protection is used. At the substations, there are disturbance fault recorders installed or relays equipped with a capability to record and store disturbance fault records. An analysis of these fault records makes a significant contribution to the efficient running of a traction system such as the Gautrain rapid rail system. A combination of the analysis of the faults that occur in the OHW as recorded and stored in the relays as well as the performance of the IEDs and the protection settings using the on-site tests are a subject of this article. en_ZA
dc.description.department Electrical, Electronic and Computer Engineering en_ZA
dc.description.librarian hj2021 en_ZA
dc.description.uri http://ieeexplore.ieee.org/xpl/RecentIssue.jsp/?punumber=4267003 en_ZA
dc.identifier.citation Moyo, N., Bansal, R. & Naidoo, R. 2021, 'Fault analysis of the Gautrain 2 × 25 kV AC traction power supply system using disturbance fault records and on-site testing', IEEE Systems Journal, vol. 15, no. 4, pp. 5704-5713. en_ZA
dc.identifier.issn 1932-8184 (print)
dc.identifier.issn 1937-9234 (online)
dc.identifier.other 10.1109/JSYST.2020.3033885
dc.identifier.uri http://hdl.handle.net/2263/80295
dc.language.iso en en_ZA
dc.publisher Institute of Electrical and Electronics Engineers en_ZA
dc.rights © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. en_ZA
dc.subject Autotransformer en_ZA
dc.subject Traction power supplies en_ZA
dc.subject Substation protection en_ZA
dc.subject Power system protection en_ZA
dc.subject Overhead wiring en_ZA
dc.subject On-site tests en_ZA
dc.subject Ground en_ZA
dc.subject Feeder en_ZA
dc.subject Fault analysis en_ZA
dc.subject Disturbance fault record (DFR) en_ZA
dc.subject Catenary en_ZA
dc.subject Current transformers (CTs) en_ZA
dc.subject Relays en_ZA
dc.subject Circuit faults en_ZA
dc.subject Substations en_ZA
dc.subject Impedance en_ZA
dc.subject Rails en_ZA
dc.subject Protective relaying en_ZA
dc.title Fault analysis of the Gautrain 2 × 25 kV AC traction power supply system using disturbance fault records and on-site testing en_ZA
dc.type Postprint Article en_ZA