Optimal coordinated control of OLTCs using Taguchi method to enhance voltage stability of power systems

Show simple item record

dc.contributor.author Ratra, Saurabh
dc.contributor.author Tiwari, Rajive
dc.contributor.author Niazi, K.R.
dc.contributor.author Bansal, Ramesh C.
dc.date.accessioned 2020-08-07T12:32:59Z
dc.date.available 2020-08-07T12:32:59Z
dc.date.issued 2019-02
dc.description 10th International Conference on Applied Energy (ICAE2018), 22-25 August 2018, Hong Kong, China en_ZA
dc.description.abstract On-load tap changer (OLTC) plays a significant role to regulate the voltage of the power system. Although some time, secondary voltage of an OLTC is pulled down when tappings are raised to restore the voltage level. This situation may finally lead to voltage collapse. To address this problem, the behavior of tap setting of OLTCs is investigated, and critical transformer and its allowed range of tap settings is identified in the paper. This paper also proposes a Taguchi based method to find optimal tap settings of OLTCs including critical transformer to improve the voltage stability margin and decrease the real power loss of the system. The proposed method is tested on IEEE 30-bus system to validate its applicability. en_ZA
dc.description.department Electrical, Electronic and Computer Engineering en_ZA
dc.description.librarian am2020 en_ZA
dc.description.uri http://www.elsevier.com/locate/procedia en_ZA
dc.identifier.citation Ratra, S., Tiwari, R., Niazi, K.R. et al. 2019, 'Optimal coordinated control of OLTCs using taguchi method to enhance voltage stability of power systems', Energy Procedia, vol. 158, pp. 3957-3963. en_ZA
dc.identifier.issn 1876-6102 (online)
dc.identifier.other 10.1016/j.egypro.2019.01.846
dc.identifier.uri http://hdl.handle.net/2263/75612
dc.language.iso en en_ZA
dc.publisher Elsevier en_ZA
dc.rights © 2019 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license . en_ZA
dc.subject L-index en_ZA
dc.subject Critical transformer en_ZA
dc.subject Tappings en_ZA
dc.subject On-load tap changer (OLTC) en_ZA
dc.subject Voltage en_ZA
dc.subject Power system en_ZA
dc.subject Taguchi based method en_ZA
dc.subject Tap settings en_ZA
dc.title Optimal coordinated control of OLTCs using Taguchi method to enhance voltage stability of power systems en_ZA
dc.type Article en_ZA


Files in this item

This item appears in the following Collection(s)