dc.description.abstract The existence of midpoint series flexible alternating current transmission system (FACTS) devices leads to degrade the performance of mho relay, leading in erroneous estimation of fault location, ie, overreach or underreach for wide variation in network parameters. This research article proposes a novel mho relay algorithm to improve the performance of distance relay in presence of FACTS device using phasor measurement unit (PMU). First, the complete model of transmission system employing static synchronous series compensator (SSSC) and its control strategy is described analytically, where the error introduced in measurement of impedance due to SSSC on the performance of distance relay. Second, a novel mho relay procedure is developed based on PMU to protect the first zone of double‐circuit transmission line for single line‐to‐ground (SLG) fault. The proposed work is analysed and simulated with 48‐pulse SSSC carried out with Bergeron model of transmission line using power system computer‐aided design (PSCAD) computer simulation. Finally, the simulation results represent that the suggested adaptive scheme is truthful, reliable, and secure with change in compensation level of SSSC. en_ZA
dc.description.department Electrical, Electronic and Computer Engineering en_ZA
dc.description.embargo 2020-04-01
dc.description.librarian hj2019 en_ZA
dc.description.uri http://wileyonlinelibrary.com/journal/etep en_ZA
dc.identifier.citation Dhenuvakonda KR, Singh A, Thakre MP, Karasani RR, Naidoo R. Adaptive digital distance relay for SSSC based double circuit transmission line using phasor measurement unit. International Transactions on Electrical Energy Systems 2019;29:e2787. https://doi.org/10.1002/etep.2787. en_ZA
dc.identifier.issn 2050-7038 (online)
dc.identifier.other 10.1002/etep.2787
dc.identifier.uri http://hdl.handle.net/2263/70313
dc.language.iso en en_ZA
dc.publisher Wiley en_ZA
dc.rights © 2018 John Wiley & Sons, Ltd. This is the pre-peer reviewed version of the following article : Adaptive digital distance relay for SSSC based double circuit transmission line using phasor measurement unit, International Transactions on Electrical Energy Systems, vol. 29, no. 6, art. e2787, pp. 1-20, 2019, doi : 10.1002/etep.2787. The definite version is available at : http://wileyonlinelibrary.com/journal/etep. en_ZA
dc.subject Protection en_ZA
dc.subject Compensator en_ZA
dc.subject Shunt en_ZA
dc.subject Algorithm en_ZA
dc.subject Adaptive distance relay en_ZA
dc.subject Static synchronous series compensator (SSSC) en_ZA
dc.subject Phasor measurement unit (PMU) en_ZA
dc.subject Power system protection en_ZA
dc.subject Power system computer‐aided design (PSCAD) en_ZA
dc.subject Electro magnetic transient design and control (EMTDC) en_ZA
dc.subject Flexible alternating current transmission system (FACTS) en_ZA
dc.title Adaptive digital distance relay for SSSC‐based double‐circuit transmission line using phasor measurement unit en_ZA
dc.type Postprint Article en_ZA


Files in this item

This item appears in the following Collection(s)

Show simple item record