dc.description.abstract |
Let-through energy (LTE) refers to the I 2 t or Joule energy that a conductor is exposed to during a fault on the feeder. This energy is influenced by the magnitude of the fault current and time it takes for the protection system to clear the fault. If the LTE exceeds the conductor thermal energy limit, the conductor will get damaged. This concept of LTE evaluation is applied to the inverse definite minimum time (IDMT) current based back-up protection elements on a multisource high-voltage feeder in a hypothetical and actual network. Another method to calculate the relay operating time for IDMT relays was developed based on an average disk speed of electromechanical over-current relay and the proportionality of its speed to the magnitude of the fault current. This method was incorporated into a software application to generate results. These results allow the user to evaluate the conductor LTE exposure, total fault time exposure, the effect of instantaneous fault clearing and the application of auto-reclose cycles. An energy-area evaluation was applied to quantify and evaluate small protection settings changes. The conclusion is that LTE analysis on back-up protection should be considered for high-voltage feeders to ensure that the conductors are protected. |
en_ZA |
dc.description.department |
Electrical, Electronic and Computer Engineering |
en_ZA |
dc.description.librarian |
hj2019 |
en_ZA |
dc.description.uri |
http://digital-library.theiet.org/content/journals/iet-gtd |
en_ZA |
dc.identifier.citation |
Slabbert, M.J., Bansal, R.C. & Naidoo, R. 2018, 'Application of let-through energy to back-up over-current protection on high-voltage feeders', IET Generation, Transmission and Distribution, vol. 12, no. 19, pp. 4341–4347. |
en_ZA |
dc.identifier.issn |
1751-8687 (print) |
|
dc.identifier.issn |
1751-8695 (online) |
|
dc.identifier.other |
10.1049/iet-gtd.2018.6190 |
|
dc.identifier.uri |
http://hdl.handle.net/2263/69023 |
|
dc.language.iso |
en |
en_ZA |
dc.publisher |
Institution of Engineering and Technology |
en_ZA |
dc.rights |
© The Institution of Engineering and Technology 2018. This paper is a postprint of a paper submitted to and accepted for publication in IET Control Theory and Applications and is subject to Institution of Engineering and Technology Copyright. The copy of record is available at IET Digital Library. |
en_ZA |
dc.subject |
Fault currents |
en_ZA |
dc.subject |
Back-up over-current protection |
en_ZA |
dc.subject |
Electromechanical over-current relay |
en_ZA |
dc.subject |
Auto-reclose cycles |
en_ZA |
dc.subject |
Fault time exposure |
en_ZA |
dc.subject |
Let-through energy (LTE) |
en_ZA |
dc.subject |
Conductor LTE exposure |
en_ZA |
dc.subject |
LTE analysis |
en_ZA |
dc.subject |
Energy-area evaluation |
en_ZA |
dc.subject |
Instantaneous fault clearing |
en_ZA |
dc.subject |
Inverse definite minimum time (IDMT) |
en_ZA |
dc.subject |
IDMT relays |
en_ZA |
dc.subject |
Multisource high-voltage feeder |
en_ZA |
dc.subject |
Conductor thermal energy limit |
en_ZA |
dc.subject |
Protection system |
en_ZA |
dc.subject |
Power system faults |
en_ZA |
dc.subject |
Conductors (electric) |
en_ZA |
dc.subject |
Power system protection |
en_ZA |
dc.subject |
Relay protection |
en_ZA |
dc.subject |
Overcurrent protection |
en_ZA |
dc.title |
Application of let-through energy to back-up over-current protection on high-voltage feeders |