dc.description.abstract |
Drag reduction in turbulent flow of hydrocarbons containing
small amounts of high polymer was first reported by Toms about
70 years ago. Previously, Mysels and his coworkers had observed
similar behavior in solutions of aluminum disoaps. A
few years later, drag reduction behavior was observed in dilute
aqueous-surfactant solutions in which long wormlike micelles
were present. In the late 1970’s this phenomenon found its first
commercial application when high molecular weight polymer
was added to crude oil flowing through the 800-mile Alyeska
pipeline. Crude flow was increased by about 25% with no additional
pumps.
However high molecular weight polymers are not suited for
use in recirculation systems because the high shear encountered
in pumps breaks the primary chemical bonds within the polymer
chains. The resulting low molecular weight polymer chain fragments
are not efficient drag reducers, and they do not reassemble.
On the other hand, surfactant micelles are held together by secondary
forces and they reform (self-associate) very quickly after
break-up in high shear regions (pumps). Thus, they are effective
in recirculation systems.
District heating systems are widely used to heat buildings in
urban locations in northern Europe and are also found in the US,
Canada, Eastern Europe and other locales. These systems circulate
hot water and exchange heat with each building thus relieving
the buildings of the need for heat sources (furnaces) and the
related investment, space, and maintenance required. They generally
utilize cheap waste heat from nearby power plants to heat
the circulating water. District cooling systems with the same advantages
are utilized in some warm climate regions, particularly
the United States and Japan. Adding a drag reducing surfactant
additive to the recirculating water could decrease pumping energy
requirements of these systems by 50% or more.
There is, however, a serious problem with this scheme as the
large reduction in friction loss is accompanied by an even larger
reduction in heat transport. Thus, to utilize drag reducing surfactant
additives in district heating or cooling systems, heat transport
must be enhanced in order to transfer heat to or from each building’s internal recirculation system.
Investigators have studied a number of heat transfer enhancement
schemes to overcome this problem focusing on temporarily
destroying the drag reducing micelle structure at the entrance to
the heat exchanger using static mixers, honeycombs, other obstructions,
ultrasonic radiation, UV radiation of photosensitive
surfactant systems, etc. and others have studied altering the turbulent
flow pattern in the heat exchanger. While some of these
were effective, generally the required energy input was too great
for them to be of practical value. These studies will be reviewed