The effect of adjacent tubes on the diabatic friction factors in the transitional flow regime

Show simple item record

dc.contributor.advisor Meyer, Josua P. en
dc.contributor.postgraduate Mulock-Houwer, Franscois Annis en
dc.date.accessioned 2016-07-29T11:02:02Z
dc.date.available 2016-07-29T11:02:02Z
dc.date.created 2016-04-15 en
dc.date.issued 2015 en
dc.description Dissertation (MEng)--University of Pretoria, 2015. en
dc.description.abstract Heat exchangers are used throughout the world in important processes such as the generation of electrical energy. Modern heat exchangers are often forced to operate in the transitional flow regime, where flow can be unpredictable. Most of the research that has been done on the transitional flow regime has focussed on the influence of heat transfer and the inlet effects. However, all these studies made use of only a single tube, while most heat exchangers would typically have a bundle of tubes such as in shell-and-tube type heat exchangers. The purpose of this study was to investigate the effect of adjacent tubes on the transitional flow regime during diabatic conditions. An experimental set-up was purposefully built for this investigation and two test sections were investigated. A single-tube test section was built for validation purposes, since similar work has been done. A triple-tube test section was built with three tubes spaced at a pitch distance of 1.4 outer diameters. The mass flow rate, as well as the pressure drops over the fully-developed section was measured for each tube. From the pressure drop data the friction factors were calculated. Furthermore, a heat flux of 3 kW/m2 was applied to each tube and the inlet, outlet and wall temperatures were measured, to ensure that specifically the diabatic friction factors were determined. Water was used as the working fluid and tests were run over a Reynolds number range of 1 000 - 6 500. An uncertainty analysis showed the maximum uncertainty of the friction factors to be 8.3%. The laminar, transitional and turbulent flow regimes could be identified from the friction factor data. The results from the single-tube test section correlated well to the literature with transition starting at a Reynolds number of 2 380 and ending at 3 050. The results from the triple-tube test section showed the start of transition to be initiated by the presence of adjacent tubes, with the Centre-tube entering transition at a Reynolds number of 1 970. The outer tubes experience a delayed start in transition at Reynolds numbers of 3 000 and 2 800 for the Left-tube and Right-tube respectively. The end of transition occurred at approximately the same Reynolds number (3 100) for all three tubes of the triple-tube test section. Since the Centre-tube entered transition earlier than the outer tubes, maldistribution was evident, with the water taking the path of least resistance. The flow rate in the Centre-tube showed an average difference of 2.8% in the Reynolds number range of 1 970 to 3 150. Maldistribution proved to be negligible when all three tubes were in the laminar or turbulent flow regimes. en
dc.description.availability Unrestricted en
dc.description.degree MEng en
dc.description.department Mechanical and Aeronautical Engineering en
dc.description.librarian tm2016 en
dc.identifier.citation Mulock-Houwer, FA 2015, The effect of adjacent tubes on the diabatic friction factors in the transitional flow regime, MEng Dissertation, University of Pretoria, Pretoria, viewed yymmdd <http://hdl.handle.net/2263/56092> en
dc.identifier.other A2016 en
dc.identifier.uri http://hdl.handle.net/2263/56092
dc.language.iso en en
dc.publisher University of Pretoria en_ZA
dc.rights © 2016 University of Pretoria. All rights reserved. The copyright in this work vests in the University of Pretoria. No part of this work may be reproduced or transmitted in any form or by any means, without the prior written permission of the University of Pretoria.
dc.subject UCTD en
dc.subject Diabatic Friction Factors
dc.subject Transitional Flow Regime
dc.subject Adjacent Tubes
dc.subject.other Engineering, built environment and information technology theses SDG-07
dc.subject.other SDG-07: Affordable and clean energy
dc.subject.other Engineering, built environment and information technology theses SDG-09
dc.subject.other SDG-09: Industry, innovation and infrastructure
dc.subject.other Engineering, built environment and information technology theses SDG-12
dc.subject.other SDG-12: Responsible consumption and production
dc.title The effect of adjacent tubes on the diabatic friction factors in the transitional flow regime en
dc.type Dissertation en