Design sensitivity analysis of using various in-tube condensation correlations for an air cooled condenser for ORCS

Show simple item record

dc.contributor.author Kaya, A.
dc.contributor.author Lazova, M.
dc.contributor.author De Paepe, M.
dc.date.accessioned 2016-07-18T11:38:28Z
dc.date.available 2016-07-18T11:38:28Z
dc.date.issued 2015
dc.description.abstract Papers presented to the 11th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics, South Africa, 20-23 July 2015. en_ZA
dc.description.abstract The study is related to the evaluation of using 19 condensation heat transfer correlations in an annular finned horizontal round tube V-shaped air-cooled condenser design problem for a representative low-temperature waste heat recovery Organic Rankine Cycle (ORC) case. The condensation is realized through cold air provided by the fan suction at a mass flow rate of 90,35 kg/s, whereas the working fluid mass flow rate is 7,8 kg/s. The considered condensation temperature is 40°C which corresponds to a saturation pressure of 1,17 bar. The ambient air is considered to be 15°C. The investigated working fluid is SES36. For a given set of geometrical constraints, an iterative condenser design model is implemented. All considered correlations are applied separately for the same boundary conditions. The design sensitivity on the overall heat transfer coefficient, total transferred heat, required fan power, air- and refrigerant-side pressure drops is assessed. By those means, the engineering error margin of using different calculation tools in designing air-cooled condensers for ORC is reported. en_ZA
dc.description.librarian am2016 en_ZA
dc.format.medium PDF en_ZA
dc.identifier.citation Kaya, A, Lazova, M & De Paepe, M 2015, 'Design sensitivity analysis of using various in-tube condensation correlations for an air cooled condenser for ORCS', Paper presented to the 11th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics, Florida, 20-23 July 2015. en_ZA
dc.identifier.isbn 97817759206873
dc.identifier.uri http://hdl.handle.net/2263/55896
dc.language.iso en en_ZA
dc.publisher International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics en_ZA
dc.rights © 2015 University of Pretoria. All rights reserved. The copyright in this work vests in the University of Pretoria. No part of this work may be reproduced or transmitted in any form or by any means, without the prior written permission of the University of Pretoria. en_ZA
dc.subject Organic Rankine Cycle en_ZA
dc.subject Temperature en_ZA
dc.subject Working fluid en_ZA
dc.subject Ambient air en_ZA
dc.title Design sensitivity analysis of using various in-tube condensation correlations for an air cooled condenser for ORCS en_ZA
dc.type Presentation en_ZA