Paper presented at the 8th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics, Mauritius, 11-13 July, 2011.
The primary purpose of this numerical investigation is to
analyze the characteristic of inside and outside flow fields of
air-cooled condenser (ACC) cell in power plant. The fin-tube
bundles are modeled using porous regions, and fan blade
passages are modeled in details to gain accurately fan exhaust
flows. Results of numerical investigation indicate that
rotational fan exhaust flows lead to inside rotational symmetry
flows and distributions of outflows from fin-tube bundles in Aframe
ACC cell. When rotational flows are in same direction of
ACC outflows in the area, high pressure increases the ACC
mass outflows. In the under corner near the ACC inlet with
inconsistent interfaces, less ACC outflows appear because of
air flows paralleling to the ACC outflow side, influenced by the
rotational flows.